저장(Save): 사양서 + 특성곡선도 + 외형도 / 인쇄(Print): 사양서 (사양서가 바르게 인쇄되기 위해서는 Internet Explorer 메뉴 [파일(F)]-[페이지설정(U)...]에서 상하좌우 여백을 '4'이하로셔야 합니다.)
HYOSUNG Low Voltage Induction Motor Data Sheet

효성 중공업

INDUCTION MOTOR
DATA SHEET

PROJECT No. 301
MODEL No. 24TE-FFEB
L-SPEC No. D1ML20603
SHEET 1 OF 1 CUSTOMER
FOR INFORMATION JOB NO. ITEM No.
SERVICE SITE QUANTITY
GENERAL DATA
GENERAL DATA
FRAME No.

250S

TYPE

TE-F

ENCLOSURE

TE

COOLING METHOD

FC(IC411)

INSULATION CLASS

F

CLASS
TEMP. RISE AT FULL LOAD
RES. METHOD

80

K (at S.F:1.0)
RATING

S1

LOCATION

OUTDOOR

ALTITUDE
LESS THAN

1000

m
HUMIDITY
LESS THAN

80

%
AMBIENT TEMP.

40

°C
EXPLOSION PROOF TYPE

N/A

MOUNTING

V1

BEARING TYPE

ANTI-FRICTION

NDE/DE BRG. No.

6313C3

/

6316C3

BRG. LUBRICATION

MOBIL Polyrex EM

PROTECTION GRADE

SERVICE FACTOR

1.15

DRIVE

DIRECT COUPLED

SHAFT
EXTENSION

SINGLE

EXTERNAL THRUST

N/A

NOISE LEVEL(MEAN VALUE AT 1m FROM MOTOR)
NO-LOAD

N/A

VIBRATION

N/A

NUMBER OF
CONSECUTIVE STARTS

N/A

ROTATION(VIEWED FROM DE)

C.C.W

PERFORMANCE DATA
PERFORMANCE DATA
OUTPUT

55

kW
POLES

6

P
ROTOR TYPE

SQUIRREL CAGE

STARTING METHOD

PHASE

3

PHASE
FREQUENCY

60

Hz
SPEED (AT FULL LOAD)

1190

r/min
PRIMARY
VOLTAGE

220

V
NO LOAD CURRENT

78.2

A
FULL LOAD CURRENT

189.7

A
LOCKED-ROTOR CURRENT

600

%
EFFICIENCY
AT 1/2 LOAD

91.5

%
AT 3/4 LOAD

93.5

%
AT FULL LOAD

94.5

%
POWER FACTOR
AT 1/2 LOAD

65.5

%
AT 3/4 LOAD

75.5

%
AT FULL LOAD

80.5

%
TORQUE
FULL LOAD

45

kg-m

441.5

N-m
LOCKED ROTOR

140

%
BREAKDOWN

190

%
MOTOR GD²

7.383

kg-m²
MAX LOAD GD² AT MOTOR SHAFT

372.9

kg-m²
MOTOR APPROX. WEIGHT

550

kg
PAINTING

0.5PB 3.2/4.4 (URETHANE)

ACCESSORIES (OPTIONAL)
ACCESSORIES (OPTIONAL)
TEMPERATURE DETECTOR
WINDING

NO

TYPE

-

BEARING

NO

TYPE

-

SPACE HEATER

NO

RATING

-

APPLICATION STANDARDS

IEC60034-1, ISO 3746

SUBMITTAL DRAWINGS
SUBMITTAL DRAWINGS
OUTLINE DIMENSION

ES1AS48768

CONDUIT BOX & COVER

ES1B100805

SPEED-TORQUE & CURRENT CURVE

D1ML20603

THERMAL LIMIT & TIME-CURRENT CURVE

D1ML20603

LOAD vs POWER FACTOR & EFFICIENCY

D1ML20603

<REMARKS>
1. ABOVE ALL DATA ARE CALCULATED AT 100% VOLTAGE.
2. PREMIUM EFFICIENCY TYPE MOTOR

SUBMITTAL DRAWINGS
REV. NO DATE PREPARED CHECKED APPROVED
1 2024-07-17 S.U.LEE J.H.CHA Y.J.PARK
<NOTE>
1. THESE DATA ARE ONLY DESIGN VALUES AND SHALL BE GUARANTEED WITH TOLERANCE OF APPLICATION STANDARD.
2. EXCEPT FOR STATEMENTS SPECIFIED ON THIS SHEET, ANYTHING ELSE SHALL BE IN ACCORDANCE WITH MAKER STANDARD
3. THE TEMPERATURE MEASURED AT BEARING HOUSING DOES NOT EXCEED 105℃.